CATEGORIES

3 Phase PME Fault Detection Unit 40R (WARB5100C/PME40R)

  • £126.65
  • 18th Ed. Compliant

    2-Year Warranty

    UK Stock

    Free Delivery £30+

    Secure Payments With

    Google Pay PayPal

    Pre-wired in the UK and built to order – allow up to 3 working days for dispatch. The WARB5100C/PME40R is a 3 Phase PME Fault Detection Unit with integrated 40A Type A RCBO. It combines a 100A MCB main switch, PME relay, and RCBO to deliver full PEN-loss protection plus...

    Pre-wired in the UK and built to order – allow up to 3 working days for dispatch.

    The WARB5100C/PME40R is a 3 Phase PME Fault Detection Unit with integrated 40A Type A RCBO. It combines a 100A MCB main switch, PME relay, and RCBO to deliver full PEN-loss protection plus overload and residual current protection for downstream circuits. Built for EV charging hubs, solar installs, and 3-phase commercial supplies, it ensures a safe and regulation-compliant setup without the need for an earth rod.

    The PME relay continuously monitors supply voltages across all three phases (400V / 415V). If undervoltage is detected (below 207V), the unit disconnects automatically and resets once stable. If overvoltage is detected (above 253V), it isolates and requires a manual reset via the red button. This ensures safe fault management under BS7671:2018+A2:2022.

    Installer Tip: Choose the 40R variant when you need combined overcurrent and residual current protection alongside PME monitoring. For sites also requiring surge protection, see the 40RSP model.

    Key Features

    • PME Fault Protection: Isolates all poles and earth on PEN loss
    • 100A MCB Main Switch: Provides upstream isolation
    • 40A Type A RCBO: Adds overload + residual current protection
    • Automatic Monitoring: Detects undervoltage & overvoltage across phases
    • Reset Functions: Auto reset on undervoltage recovery; manual reset for overvoltage
    • Compliance: BS7671:2018+A2:2022 PME requirements met
    • Applications: EV chargers, solar PV installs, and commercial 3-phase sites

    Variant Comparison

    Model Configuration Best Use Case
    WARB5100C/PME 100A MCB + PME Relay Base option for PME detection only
    WARB5100C/PMESP 100A MCB + PME Relay + SPD Adds surge protection for EV & solar sites
    WARB5100C/PME40R (This Product) 100A MCB + PME Relay + 40A RCBO Adds overload + residual protection
    WARB5100C/PME40RSP 100A MCB + PME Relay + 40A RCBO + SPD Full coverage with surge + RCBO protection
    WARB5100C/PME63DRSP 100A MCB + PME Relay + 63A RCBO + SPD Higher load three-phase installs with full protection

    What does the RCBO add to this unit?

    The factory-fitted 40A RCBO adds both overload and residual current protection, providing extra safety compared to the base or SPD-only models.

    Do I still need an earth rod?

    No. The PME relay removes the need for an earth rod, ensuring faster and compliant installs.

    Can this unit be used with EV chargers?

    Yes – it’s compatible with most 3-phase EV chargers, including Tesla Wall Connectors, especially where built-in PME protection is absent.

    What’s the difference between this and the 40RSP?

    The 40RSP model includes the same RCBO plus a Type 2 SPD for surge protection. Choose based on site risk and compliance needs.

    Is this compliant with BS7671?

    Yes – it fully complies with BS7671:2018+A2:2022, including PME requirements.

    Product Code WARB5100C/PME40R
    Rated Voltage 400V / 415V (3 Phase)
    Voltage Monitoring Range 207V – 253V per phase
    Main Switch 100A Curve C MCB (5-pole)
    RCBO 40A Type A RCBO
    Frequency 50Hz
    Ingress Rating IP40 (indoor use)
    Reset Functions Auto reset (undervoltage), Manual reset (overvoltage)
    Standards BS EN 61439-3, BS7671:2018+A2:2022
    Build Time 3 working days from order

    This PME fault detection unit with RCBO is supplied pre-wired, labelled, and ready for connection. Installation must be carried out by a qualified electrician in accordance with BS7671:2018+A2:2022.

    • Isolate mains before installation
    • Fit with correct gland fittings and torque (2.5Nm)
    • Test PME relay and RCBO operation during commissioning
    • Install indoors in a ventilated location (IP40 rated)