A-Type RCBO EV Kit – 2 Way 32 A C Curve (WMEV232C)
18th Ed. Compliant
2-Year Warranty
UK Stock
Free Delivery £30+
Secure Payments With
The WMEV232C is a 2-way A-Type RCBO EV Kit fitted with a 32 A C-curve high-immunity Type A RCBO. It provides overload, short-circuit and earth-leakage protection (30 mA AC + 6 mA DC) fully in line with 18th Edition Amendment 2 requirements. This configuration is ideal for 7 kW single-phase...
The WMEV232C is a 2-way A-Type RCBO EV Kit fitted with a 32 A C-curve high-immunity Type A RCBO. It provides overload, short-circuit and earth-leakage protection (30 mA AC + 6 mA DC) fully in line with 18th Edition Amendment 2 requirements.
This configuration is ideal for 7 kW single-phase EV chargers that draw noticeable startup inrush currents due to transformers or filtering components. The C-curve trip profile (5–10 × In) offers surge tolerance without sacrificing response speed under faults. Compact and factory-wired, it delivers reliable dual-pole isolation for modern domestic and light-commercial installs.
Installer Tip: Use the 32 A C-curve kit for 7 kW EV chargers with transformer or switch-mode inputs that produce brief inrush currents. If your charger has a low-inrush design, the 32 A B-curve version is sufficient.
- 32 A C-curve Type A RCBO (30 mA AC + 6 mA DC detection)
- Dual-pole (1P + N) isolation – disconnects live and neutral
- Compact 2-way steel enclosure with hinged cover
- High-immunity design reduces false trips on EV loads
- Complies with BS EN 61009-1 and BS 7671 (A2)
| Part Code | Rating | Curve | Typical Use |
|---|---|---|---|
| WMEV225C | 25 A | C | 5–6 kW chargers / light commercial feeds |
| WMEV232C | 32 A | C | 7 kW EV chargers on dedicated radials |
| WMEV240C | 40 A | C | High-load or dual-socket EV installations |
Each kit is pre-built and ready to install. For PEN-fault and load-balancing compliance, pair with our PME Fault Detection Unit. Add a Single Module SPD for surge defence where required.
When should I choose the 32 A C Curve variant?
Use it for 7 kW EV chargers that draw moderate inrush currents or have transformer inputs. It prevents nuisance tripping while remaining fully compliant.
Is this kit 18th Edition compliant?
Yes – it includes a Type A RCBO with 30 mA AC + 6 mA DC detection as required under Amendment 2.
Does it isolate both live and neutral?
Yes – the 1P + N RCBO disconnects both conductors for safe maintenance and fault clearance.
Can I add surge protection?
Yes – fit a Single Module SPD or an upstream surge unit as required by design.
Is it suitable for solar PV as well as EV circuits?
Yes – the Type A RCBO is bi-directional and approved for both EV and PV applications.
- Part Code: WMEV232C
- Enclosure: 2-way steel with hinged lid
- Device: Type A RCBO (high immunity)
- Rated Current (In): 32 A
- Curve: C
- Earth Leakage: 30 mA AC + 6 mA DC
- Breaking Capacity: 6 kA
- Poles: 1P + N (switched neutral)
- Standards: BS EN 61009-1; BS 7671:2018 (A2)
- Typical Use: 7 kW EV chargers with transformer input or moderate inrush current
The WMEV232C kit is supplied pre-assembled for rapid fit-out. All installation and testing must be performed by a qualified electrician.
- Mount indoors or within an IP-rated housing if external
- Select 32 A C-curve for 7 kW chargers with transformer or inrush profiles
- Verify Zs, R1 + R2 and disconnection times to BS 7671 (A2)
- Add SPD protection if specified by site design or manufacturer