The WKC216C is a 16 A 2 Pole 10 kA Miniature Circuit Breaker (MCB) designed for small-power and control circuits with moderate inrush currents. The C-curve tripping profile provides a short delay at start-up — ideal for motors, fans, heating controls, and automation panels where current peaks are common. Dual-pole...

Read full description

Accepted payment methods

  • American Express
  • Apple Pay
  • Diners Club
  • Discover
  • Google Pay
  • Maestro
  • Mastercard
  • PayPal
  • Shop Pay
  • Union Pay
  • Visa

Free delivery over £80 Delivery information

Need help choosing the right configuration? Call 01923 969 309

Description

The WKC216C is a 16 A 2 Pole 10 kA Miniature Circuit Breaker (MCB) designed for small-power and control circuits with moderate inrush currents. The C-curve tripping profile provides a short delay at start-up — ideal for motors, fans, heating controls, and automation panels where current peaks are common.

Dual-pole isolation ensures both live conductors are disconnected simultaneously, meeting BS EN 60898-1 standards for circuit protection and safety. Compact 36 mm body fits any 35 mm DIN rail enclosure including consumer units, modular enclosures, and commercial boards.

Installer Tip: Use a 16 A C-curve on small motor or control circuits where a B-curve may nuisance trip. For purely resistive loads, the B-curve version is suitable, while D-curves suit high inrush equipment.

Key Features

  • 16 A rated – ideal for small motor and control applications
  • 10 kA breaking capacity – suitable for commercial fault levels
  • 2-pole design – isolates both live conductors together
  • C-curve tripping – allows moderate inrush without unwanted trips
  • Bi-directional terminals – can be wired from line or load end
  • 36 mm width – compact DIN-rail footprint
  • Fully compliant with IEC/EN 60898-1 and the 18th Edition Wiring Regulations

Compare 2 Pole 10 kA MCB Variants

Model Rating Curve
WKC216B 16 A B Curve
WKC216C (This Product) 16 A C Curve
WKC216D 16 A D Curve
Technical specs
  • Model: WKC216C
  • Poles: 2
  • Rated Current: 16 A
  • Curve Type: C
  • Breaking Capacity: 10 kA
  • Operating Voltage: 230/400 V AC
  • Mounting: 35 mm DIN rail (EN 60715)
  • Width: 36 mm (2 modules)
  • Standard: IEC/EN 60898-1
  • Applications: Motors, control gear, fans, heating spurs
Installation notes

To be installed by a qualified electrician to BS 7671. Confirm correct cable size, circuit rating, and curve selection before fitting.

  • Mount on 35 mm DIN rail (EN 60715)
  • Torque terminals to 2.0–2.5 Nm
  • Verify insulation resistance and polarity prior to energising
  • Record and label protected circuits within the distribution schedule
FAQs

What applications suit a 16 A C-curve MCB?

Used for small motors, control gear, and heating circuits where inrush current might cause a B-curve breaker to trip prematurely.

Does it disconnect both conductors?

Yes – 2-pole operation isolates both live lines simultaneously for safe maintenance.

Is it compliant with BS EN 60898-1?

Yes – tested to BS EN 60898-1 and fully compliant with the 18th Edition Wiring Regulations.

Can it be used for automation panels?

Yes – commonly installed in control or automation panels feeding motors or relays with brief inrush surges.

Reviews

Power & Data UK

Why buy from Power & Data?

  • Electrical ranges in one place

    Consumer units, circuit protection and ranges for renewable installations.

    Explore the range
  • Speak to P&D

    Have a question before you order? Call our sales team.

    01923 969 309
  • Secure checkout

    Choose from the payment methods available at checkout, with your order total shown before you pay.