CATEGORIES

6kA MCB – 40A 1 Pole B Curve (WMC140B)

£2.20 ex VAT £2.64 inc VATWas £2.99 ex VAT
SKU: WMC140B

The WMC140B is a 40 A single-pole 6 kA Miniature Circuit Breaker (MCB) built for high-load domestic and light-commercial circuits such as sub-mains, electric heaters and distribution feeds. Its B-curve tripping profile (3–5 × In) delivers fast, reliable protection against overcurrent and short-circuit faults while minimising nuisance tripping on steady-load...

Read full description

Accepted payment methods

  • American Express
  • Apple Pay
  • Diners Club
  • Discover
  • Google Pay
  • Maestro
  • Mastercard
  • PayPal
  • Shop Pay
  • Union Pay
  • Visa

Free delivery over £80 Delivery information

Need help choosing the right configuration? Call 01923 969 309

Description

The WMC140B is a 40 A single-pole 6 kA Miniature Circuit Breaker (MCB) built for high-load domestic and light-commercial circuits such as sub-mains, electric heaters and distribution feeds. Its B-curve tripping profile (3–5 × In) delivers fast, reliable protection against overcurrent and short-circuit faults while minimising nuisance tripping on steady-load circuits.

Fully tested to BS EN 60898, this MCB fits all Whitecliffe consumer units and standard DIN-rail enclosures. It offers a 6 kA breaking capacity and a 20 000-cycle mechanical life, making it a dependable choice for domestic and small-commercial distribution applications.

Installer Tip: Ideal for sub-main feeds or heavy fixed loads drawing up to 40 A. Confirm cable size and protective coordination to maintain BS 7671 disconnection times and voltage-drop limits.

  • 40 A rated current with B-curve (3–5 × In) tripping
  • 6 kA breaking capacity at 230/400 V AC
  • Single-pole design – 18 mm module width
  • DIN-rail mounted for consumer units and distribution boards
  • Complies with BS EN 60898 and BS 7671 (18th Edition A2)
  • Tested service life – 20 000 mechanical / 8 000 electrical operations
  • Contact position indicator for visual status check
Part Code Rating Curve Typical Use
WMC132B 32 A B Cookers, heaters and fixed equipment
WMC140B 40 A B Sub-mains and high-load feed circuits
WMC150B 50 A B Feed circuits and plant equipment
WMC140C 40 A C Motors, compressors or loads with higher inrush

The WMC140B offers robust 6 kA fault protection for high-load radial and sub-main circuits. For installations with motors or transformer inrush, view our C Curve MCB range or use Type A RCBOs for combined overcurrent and earth-fault protection.

Technical specs
  • Part Code: WMC140B
  • Type: Single Pole MCB
  • Rated Current (In): 40 A
  • Curve: B (3–5 × In tripping characteristic)
  • Rated Voltage (Ue): 230/400 V AC
  • Rated Frequency: 50/60 Hz
  • Breaking Capacity (Icn): 6 kA
  • Insulation Voltage (Ui): 500 V
  • Impulse Withstand (Uimp): 4 kV
  • Dielectric Test Voltage: 2 kV for 1 minute
  • Thermal Reference Temp: 30 °C
  • Operating Temperature: –5 °C to +40 °C (avg < 35 °C)
  • Mechanical Life: 20 000 operations
  • Electrical Life: 8 000 operations
  • Mounting: 35 mm DIN rail (1 module width)
  • Standards: BS EN 60898; BS 7671:2018 (Amendment 2)
  • Typical Applications: Sub-mains, distribution feeds and high-load equipment circuits
Installation notes

Install the WMC140B only in a suitable consumer unit or distribution board by a qualified electrician. Confirm the device rating and curve type match the circuit design and upstream protective device.

  • Mount securely on DIN rail and verify busbar alignment
  • Use B-curve for steady high-load circuits and sub-mains
  • Ensure cable size and Zs values meet BS 7671 limits
  • Consider C-curve for inrush-sensitive loads (motors, compressors)
  • Tighten terminals to manufacturer torque values and record results
FAQs

Where is a 40 A B Curve MCB used?

Typically on sub-main feeds and high-load radial circuits such as heaters or small distribution boards. B-curve devices provide fast fault clearing at 3–5 × In.

Is the WMC140B compatible with Whitecliffe boards?

Yes – it fits all Whitecliffe consumer units and standard 18 mm DIN-rail enclosures.

Can this breaker be used to feed an outbuilding?

Yes, if the sub-main cable and enclosure meet regulation requirements. Use our IP65 plastic enclosure for outdoor installs.

When should I use a C Curve MCB instead?

Choose a C Curve MCB if your circuit includes motors or equipment with high inrush currents that could trip a B curve device.

What does 6 kA mean?

It’s the breaker’s rated breaking capacity – the maximum fault current it can safely interrupt. For higher fault-level sites, see our 10 kA MCB range.

Reviews

Power & Data UK

Why buy from Power & Data?

  • Electrical ranges in one place

    Consumer units, circuit protection and ranges for renewable installations.

    Explore the range
  • Speak to P&D

    Have a question before you order? Call our sales team.

    01923 969 309
  • Secure checkout

    Choose from the payment methods available at checkout, with your order total shown before you pay.