3-Pole Type A RCBO – 32A C Curve 30mA 10kA (WRT332C-030)
18th Ed. Compliant
2-Year Warranty
UK Stock
Free Delivery £80+
Secure Payments With
The WRT332C-030 is a 3-pole Type A RCBO designed to provide combined residual current and overcurrent protection for three-phase installations. Rated at 32A with a C curve tripping characteristic and 30mA sensitivity, it protects circuits against overload, short-circuit, and earth leakage faults in a compact 3-module format. Type A protection...
The WRT332C-030 is a 3-pole Type A RCBO designed to provide combined residual current and overcurrent protection for three-phase installations. Rated at 32A with a C curve tripping characteristic and 30mA sensitivity, it protects circuits against overload, short-circuit, and earth leakage faults in a compact 3-module format.
Type A protection enables detection of AC residual currents and pulsating DC components, making this RCBO suitable for modern electrical systems with electronic or inverter-based loads. The C curve response allows it to accommodate moderate inrush currents, commonly found in motors, commercial equipment, and mixed-load distribution boards.
Installer note: Switched neutral operation ensures L1, L2, L3, and N are disconnected together, improving safety and simplifying insulation resistance testing.
- 3-pole Type A RCBO with integrated overcurrent protection
- 32A rated current with C curve characteristic
- 30mA residual current sensitivity
- 10kA short-circuit breaking capacity
- Switched neutral for full circuit isolation
- Compact 3-module DIN rail design
- Clear IN / OUT / LOAD terminal markings
| Part Code | Rating | Curve | Residual Current |
|---|---|---|---|
| WRT332C-030 | 32A | C Curve | 30mA |
| WRT320C-030 | 20A | C Curve | 30mA |
| WRT332B-030 | 32A | B Curve | 30mA |
| WRT340B-030 | 40A | B Curve | 30mA |
| WRT340C-030 | 40A | C Curve | 30mA |
| WRT350C-030 | 50A | C Curve | 30mA |
The WRT332C-030 is suited to three-phase circuits where Type A protection and tolerance for moderate inrush currents are required without compromising residual current safety.
What is the difference between B curve and C curve RCBOs?
C curve RCBOs allow higher inrush currents than B curve devices, making them suitable for motor-driven or mixed-load circuits.
Does this RCBO include a switched neutral?
Yes. The neutral is switched, providing full disconnection of all live conductors.
Is this suitable for three-phase commercial installations?
Yes. It is designed for three-phase commercial, industrial, and advanced residential circuits where Type A protection is required.
What is the breaking capacity of this RCBO?
The WRT332C-030 has a rated short-circuit breaking capacity of 10kA.
Is this device supplied pre-wired?
No. It is supplied as a DIN-rail-mounted RCBO and must be wired during installation.
- Device Type: 3-Pole RCBO
- Residual Current Type: Type A
- Rated Current: 32A
- Tripping Curve: C Curve
- Residual Current Sensitivity: 30mA
- Breaking Capacity: 10kA
- Number of Modules: 3
- Neutral: Switched
- Mounting: DIN rail (EN 60715)
- Rated Voltage: 230V AC
- Frequency: 50/60Hz
- Compliance: IEC / EN 61009-1
This RCBO must be installed by a qualified electrician as part of a three-phase distribution board. Ensure correct termination of supply and load conductors.
- Mount on a standard 35mm DIN rail
- Observe IN / OUT / LOAD markings during installation
- Do not connect incoming supply to load terminals
- Switched neutral allows safe isolation during testing
- Confirm C curve suitability for motor or mixed-load circuits