CATEGORIES

3-Pole Type A RCBO – 32A C Curve 30mA 10kA (WRT332C-030)

  • £75.85
  • 18th Ed. Compliant

    2-Year Warranty

    UK Stock

    Free Delivery £80+

    Secure Payments With

    Google Pay PayPal

    The WRT332C-030 is a 3-pole Type A RCBO designed to provide combined residual current and overcurrent protection for three-phase installations. Rated at 32A with a C curve tripping characteristic and 30mA sensitivity, it protects circuits against overload, short-circuit, and earth leakage faults in a compact 3-module format. Type A protection...

    The WRT332C-030 is a 3-pole Type A RCBO designed to provide combined residual current and overcurrent protection for three-phase installations. Rated at 32A with a C curve tripping characteristic and 30mA sensitivity, it protects circuits against overload, short-circuit, and earth leakage faults in a compact 3-module format.

    Type A protection enables detection of AC residual currents and pulsating DC components, making this RCBO suitable for modern electrical systems with electronic or inverter-based loads. The C curve response allows it to accommodate moderate inrush currents, commonly found in motors, commercial equipment, and mixed-load distribution boards.

    Installer note: Switched neutral operation ensures L1, L2, L3, and N are disconnected together, improving safety and simplifying insulation resistance testing.

    • 3-pole Type A RCBO with integrated overcurrent protection
    • 32A rated current with C curve characteristic
    • 30mA residual current sensitivity
    • 10kA short-circuit breaking capacity
    • Switched neutral for full circuit isolation
    • Compact 3-module DIN rail design
    • Clear IN / OUT / LOAD terminal markings
    Part Code Rating Curve Residual Current
    WRT332C-030 32A C Curve 30mA
    WRT320C-030 20A C Curve 30mA
    WRT332B-030 32A B Curve 30mA
    WRT340B-030 40A B Curve 30mA
    WRT340C-030 40A C Curve 30mA
    WRT350C-030 50A C Curve 30mA

    The WRT332C-030 is suited to three-phase circuits where Type A protection and tolerance for moderate inrush currents are required without compromising residual current safety.

    What is the difference between B curve and C curve RCBOs?

    C curve RCBOs allow higher inrush currents than B curve devices, making them suitable for motor-driven or mixed-load circuits.

    Does this RCBO include a switched neutral?

    Yes. The neutral is switched, providing full disconnection of all live conductors.

    Is this suitable for three-phase commercial installations?

    Yes. It is designed for three-phase commercial, industrial, and advanced residential circuits where Type A protection is required.

    What is the breaking capacity of this RCBO?

    The WRT332C-030 has a rated short-circuit breaking capacity of 10kA.

    Is this device supplied pre-wired?

    No. It is supplied as a DIN-rail-mounted RCBO and must be wired during installation.

    • Device Type: 3-Pole RCBO
    • Residual Current Type: Type A
    • Rated Current: 32A
    • Tripping Curve: C Curve
    • Residual Current Sensitivity: 30mA
    • Breaking Capacity: 10kA
    • Number of Modules: 3
    • Neutral: Switched
    • Mounting: DIN rail (EN 60715)
    • Rated Voltage: 230V AC
    • Frequency: 50/60Hz
    • Compliance: IEC / EN 61009-1

    This RCBO must be installed by a qualified electrician as part of a three-phase distribution board. Ensure correct termination of supply and load conductors.

    • Mount on a standard 35mm DIN rail
    • Observe IN / OUT / LOAD markings during installation
    • Do not connect incoming supply to load terminals
    • Switched neutral allows safe isolation during testing
    • Confirm C curve suitability for motor or mixed-load circuits