    The WFD116B-030 is a 16A, B Curve Arc Fault Detection (AFDD) RCBO, providing arc fault detection, residual current protection (30mA), short-circuit, and overload protection in one device. Designed to BS 7671:2018 (18th Edition) standards, it offers advanced fire prevention and peace of mind for installers and property owners. Unlike standard...

    The WFD116B-030 is a 16A, B Curve Arc Fault Detection (AFDD) RCBO, providing arc fault detection, residual current protection (30mA), short-circuit, and overload protection in one device. Designed to BS 7671:2018 (18th Edition) standards, it offers advanced fire prevention and peace of mind for installers and property owners.

    Unlike standard RCBOs, this AFDD RCBO includes a microprocessor-driven arc detection system. It monitors the electrical waveform and trips instantly when dangerous arc impulses occur, caused by damaged cables, loose terminations, faulty appliances, or ageing wiring. Both live and neutral poles are disconnected, ensuring complete circuit isolation.

    Installer Tip: The 16A version is well-suited to kitchen ring circuits, small power circuits, and areas with higher load appliances where fire protection is a must.

    Protective Coverage

    This AFDD RCBO protects against:

    • Arc faults – series and parallel
    • Residual current leakage – Type A (AC + pulsed DC)
    • Overload and short-circuit conditions
    • Overvoltage – trips at 275V ±5%

    Variant Comparison

    Model Rating Curve Sensitivity
    WFD106B-030 6A B Curve 30mA
    WFD110B-030 10A B Curve 30mA
    WFD116B-030 (This Product) 16A B Curve 30mA
    WFD120B-030 20A B Curve 30mA
    WFD132B-030 32A B Curve 30mA
    WFD140B-030 40A B Curve 30mA

    What is the WFD116B-030 used for?

    Best suited for small power circuits, kitchen rings, and areas with higher fire risk. It offers full AFDD protection in a compact 1-module device.

    Does this device isolate both live and neutral?

    Yes – the switched neutral design provides complete circuit isolation for safety.

    Is it compliant with UK regulations?

    Yes – it complies with BS 7671:2018+A2 and is certified to BS EN AFDD and RCBO standards.

    What’s the main difference between a 16A AFDD RCBO and a standard 16A RCBO?

    The AFDD RCBO detects arc faults caused by damaged wiring or poor connections, which standard RCBOs cannot detect.

    What other sizes are available?

    The WFD1 Series includes 6A, 10A, 20A, 32A, and 40A models. This page covers the 16A WFD116B-030.

    • SKU: WFD116B-030
    • Type: AFDD + Type A RCBO
    • Rating: 16A
    • Curve: B
    • Residual Current Sensitivity: 30mA
    • Breaking Capacity: 6kA
    • Operating Voltage: 230V AC, 50Hz
    • Arc Fault Detection: Series & Parallel faults
    • Additional Protection: Overload, short circuit, earth leakage, overvoltage (275V ±5%)
    • Isolation: Disconnects live & neutral (switched neutral)
    • Mounting: 1 module DIN rail
    • Dimensions: 17.8 × 116 × 76 mm
    • Compliance: BS EN 61009-1, BS EN 62606, BS 7671:2018 (18th Edition)

    Must be installed by a qualified electrician in accordance with BS 7671. AFDD RCBOs are recommended for circuits with sleeping accommodation or increased fire risk.

    • Use the 16A model for small power and kitchen ring circuits
    • Single-phase 230V AC operation only
    • DIN rail mounted, 1 module wide (17.8mm)
    • Not designed for DC networks
    • Fully compatible with WCED consumer units